Damage Analysis of a 250 kVA Distribution Transformer UNINDO Brand Using a Multi-Parameter Approach TTR, IR, and Visual Inspection

Authors

  • Dimas Airlangga Nugraha Universitas Siliwangi
  • Linda Faridah Universitas Siliwangi

Keywords:

Distribution Transformer, Transformer Turns Ratio (TTR), Insulation Resistance (IR), Visual Inspection

Abstract

Distribution transformers play an important role in ensuring the continuity of electrical energy distribution, so an accurate diagnostic method is needed to detect damage. This study aims to analyze the condition of a 250 kVA UNINDO brand distribution transformer using a multi-parameter approach through Transformer Turns Ratio (TTR), Insulation Resistance (IR), and visual inspection tests. TTR testing was carried out at seven tap positions, while IR testing used a voltage of 5 kV. The results showed that phases A and B were still within the tolerance limit of ±1%, while phase C did not show a ratio reading indicating open winding. Very low insulation resistance values (0.02-0.05 MΩ) indicated significant insulation degradation. These findings were reinforced by visual inspections that showed physical damage and indications of overheating in the phase C winding. This study confirmed that the integration of TTR, IR, and visual inspection methods was able to improve the accuracy of transformer damage diagnosis and support condition-based maintenance decision making in the field.

References

K. Ridwan, “Analisa Perkiraan Umur Transformator Distribusi Berdasarkan Pembebanan Dengan Metode Tingkat Tahunan,” J. Fokus Elektroda Energi List. Telekomun. Komputer, Elektron. dan Kendali), vol. 2, no. 4, pp. 1–5, 2017, doi: 10.33772/jfe.v2i4.7899.

C. N. Anshar, “Studi Analisa Perkiraan Umur Transformator Distribusi 20 KV Akibat Pembebanan,” J. Tek. Komputer, Agroteknologi Dan Sains, vol. 1, no. 2, pp. 247–253, 2023, doi: 10.56248/marostek.v1i2.26.

S. Tenbohlen, S. Coenen, M. Djamali, A. Müller, M. H. Samimi, and M. Siegel, “Diagnostic measurements for power transformers,” Energies, vol. 9, no. 5, pp. 1–25, 2016, doi: 10.3390/en9050347.

C. Ranga, A. K. Chandel, and R. Chandel, “Condition assessment of power transformers based on multi-attributes using fuzzy logic,” IET Sci. Meas. Technol., vol. 11, no. 8, pp. 983–990, 2017, doi: 10.1049/iet-smt.2016.0497.

G. Kaliappan and M. Rengaraj, “Aging assessment of transformer solid insulation: A review,” Mater. Today Proc., vol. 47, no. xxxx, pp. 272–277, 2021, doi: 10.1016/j.matpr.2021.04.301.

M. M. Islam, G. Lee, and S. N. Hettiwatte, “A review of condition monitoring techniques and diagnostic tests for lifetime estimation of power transformers,” Electr. Eng., vol. 100, no. 2, pp. 581–605, 2018, doi: 10.1007/s00202-017-0532-4.

N. Mavrikakis and K. Siderakis, “Effects of Aging on Condition of In-Service Transformer Oil: The Study Case of 150 kV/20 kV Substations in Crete,” Energies, vol. 18, no. 18, pp. 1–19, 2025, doi: 10.3390/en18184900.

S. Suganda and A. Muis, “Analisa Kualitas Tahanan Isolasi Transformator Daya,” Sinusoida, vol. 23, no. 2, pp. 1–10, 2021, doi: 10.37277/s.v23i2.1114.

N. Hudayani, I. Hasanuddin, A. Hafid, and Z. Zainuddin, “Analysis of Transformer OilQuality at PT. PLN ULTG PANAKKUKANG,” Multidisiplin Saintek, vol. 01, no. 03, 2023, [Online]. Available: https://ejournal.warunayama.org/kohesi

M. M. Sanaky, “Jurnal Simetrik,” J. Simetrik, vol. 11, no. 1, pp. 432–439, 2021.

Almas, Syukri, and Muliadi, “Analisis Pengaruh Pembebanan Lebih pada Trafo Distribusi GH Krueng Cut Banda Aceh,” Aceh J. Electr. Eng. Technol., vol. 4, no. 2, pp. 6–10, 2024.

C. P. Maharani, I. M. A. Nrartha, S. I. Nugroho, and A. Hasibuan, “Pengujian Tegangan Tembus Minyak Trafo,” vol. 12, no. 3, pp. 248–256, 2024.

M. H. Indra, Y. S. H, and I. Priyadi, “Pengujian Tahanan Isolasi Pada Transformator Distribusi 160,” … J. Ilm. Bid. …, vol. 12, no. 2, pp. 8–15, 2022, [Online]. Available: https://ejournal.unib.ac.id/jamplifier/article/view/25274%0Ahttps://ejournal.unib.ac.id/jamplifier/article/download/25274/11758

M. Shofiyuddin and A. Wisaksono, “Testing of The Insulation Resistance and Turns Test Ratio (TTR) of The Distribution Transformers at PT PLN (Pesero) UP3 Sidoarjo,” Procedia Eng. Life Sci., vol. 7, pp. 339–344, 2024, doi: 10.21070/pels.v7i0.1478.

C. Hu et al., “Localization and Diagnosis of Short-Circuit Faults in Transformer Windings Injected by Damped Oscillatory Wave,” Energies, vol. 17, no. 24, 2024, doi: 10.3390/en17246259.

T. Committee, I. Power, and E. Society, IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers , Regulators , and Reactors IEEE Power and Energy Society, vol. 2013. 2013.

E. Machinery and P. Engineering, “IEEE Recommended Practice for Testing Insulation Resistance of Rotating Machinery,” vol. 2000, 2006.

N. Rosyidi et al., “ANALISIS PENGUKURAN TRANSFORMATOR 400 KVA MENGGUNAKAN ON LOAD TAP CHARGER,” vol. XXIV, pp. 1–8, 2022.

P. Mwinisin, A. Mingotti, L. Peretto, R. Tinarelli, and M. Tefferi, “Electrical Diagnosis Techniques for Power Transformers: A Comprehensive Review of Methods, Instrumentation, and Research Challenges,” Sensors, vol. 25, no. 7, pp. 1–38, 2025, doi: 10.3390/s25071968.

Published

2026-06-29